Eaton | MTL IOP digital & analogue I/O surge protector
The MTL IOP Digital & Analogue I/O Surge Protector is a high-performance solution designed to protect digital and analogue input/output (I/O) systems from damaging power surges, lightning strikes, and transient overvoltages. Engineered for industrial automation and control applications, the MTL IOP ensures reliable safeguarding of sensitive I/O equipment, maintaining operational continuity and system accuracy. With its robust design and compliance with global standards, the MTL IOP is the ideal choice for protecting I/O systems in harsh environments.
Key Features of MTL IOP Surge Protector
- Comprehensive I/O Protection
- Protects both digital and analogue I/O systems from surges and transients.
- Ensures reliable operation in industrial automation and control systems.
- High Surge Current Capacity
- Handles high surge currents, providing robust protection for sensitive I/O equipment.
- Fast Response Time
- Responds to surges in nanoseconds, offering instant protection.
- Compact and Durable Design
- Space-saving and rugged, suitable for installation in control panels or field enclosures.
- Built to withstand harsh industrial environments.
- Compliance with Global Standards
- Meets IEC 61643 and UL 1449 standards, ensuring safety and reliability.
- Low Insertion Loss
- Ensures minimal impact on signal integrity, maintaining the accuracy of I/O systems.
- Easy Installation and Maintenance
- Modular design allows for quick installation and replacement.
- Visual indicators for easy status monitoring.
Applications of MTL IOP Surge Protector
- Industrial Automation: Protects PLCs, SCADA systems, and control networks.
- Process Control Systems: Safeguards I/O systems in manufacturing and processing plants.
- Telecommunication Networks: Ensures reliable protection for communication lines and equipment.
- Building Management Systems: Protects I/O systems in HVAC, security, and lighting systems.
- Renewable Energy Systems: Shields I/O systems in solar and wind power installations.
Benefits of MTL IOP Surge Protector
- Enhanced Equipment Protection: Prevents damage to digital and analogue I/O systems from power surges and transients.
- Reduced Downtime: Minimizes operational disruptions caused by electrical disturbances.
- Cost Savings: Avoids expensive repairs and equipment replacements.
- Improved Safety: Protects personnel and equipment from hazardous voltage spikes.
- Reliable Performance: Ensures continuous operation in harsh industrial environments.
Installation and Maintenance Tips
- Install the surge protector as close as possible to the I/O system being protected.
- Ensure proper grounding and bonding to optimize performance.
- Regularly monitor the device’s status and replace it if indicators show end-of-life or failure.
Why Choose MTL IOP Surge Protector?
The MTL IOP Digital & Analogue I/O Surge Protector is trusted by industries worldwide for its advanced protection capabilities, robust design, and compliance with global standards. Whether you’re protecting industrial automation systems, process control networks, or telecom infrastructure, the MTL IOP delivers unmatched reliability and performance for I/O system protection.
Protect Your I/O Systems with MTL IOP
Don’t let power surges compromise your operations or damage your I/O systems. Invest in the MTL IOP Digital & Analogue I/O Surge Protector to ensure the safety and reliability of your industrial I/O systems. Contact us today to learn more or to find the perfect solution for your needs!
Keywords: MTL IOP, digital I/O surge protection, analogue I/O surge protection, industrial surge protection, process control surge protection, lightning protection, transient overvoltage protection, IEC 61643, UL 1449, renewable energy surge protection, modular surge protection design.
TO ORDER SPECIFY – Order by module, as listed in the specification table below. | |||||
Model | IOP32 | IOP32D | IOP HC32 | IOP-AC | |
Nominal voltage | Un | 32V | 32V | 32V | 240V |
Rated voltage (MCOV) | Uc | 36V | 36V | 36V | 275V |
Nominal current | In | 675mA | 675mA | 5A | 1.75A |
Nominal discharge current (8/20µs) | isn | 3kA | 3kA | 3kA | 3kA |
Max discharge current (8/20µs) | Imax | 20kA | 20kA | 20kA | 20kA |
Lightning impulse current (10/350µs) | Iimp | 2.5kA | 2.5kA | 2.5kA | 2.5kA |
Residual voltage @ isn | Up | 45V L-L 78V L-G |
45V L-L 90V L-G |
65VL-L (250V sparkover) 65V L-G |
800V L-L 800V L-G |
Voltage protection level @ 1kV/µs | Up | <38V | <38V | <38V | 500V |
Bandwidth | fG | 6.5MHz | 6.5MHz | N/A | N/A |
Series resistance | R | 2Ω | 2Ω | 0Ω | 0.5Ω |
Category tested | A2, B2, C1, C2, C3, D1 | ||||
Overstressed fault mode in=3kA | 22kA | 22kA | 22kA | 22kA | |
Impulse durability (8/20µs) | 10kA | 10kA | 10kA | 10kA | |
Degree of protection | IP20 | ||||
AC durability | 1Arms, 5T | N/A | |||
Service conditions | 80kPa- 160kPa 5%- 95% RH | ||||
Tested in accordance with IEC 61643-21. |
Please contact us by email sales@ghitech.co.id for assistance and technical support. All questions are welcome!
Related Products
-
CEAG nLLK 15 LED Non-metallic Hazardous Area Linear Light Fixtures
Crouse-Hinds series nLLK 15 LED light fixtures utilize long-life LED tubes to provide general illumination, indoors or out, in IEC…
-
CEAG eLLK Non-metallic Hazardous Area Linear LED Light Fixtures
The Crouse-Hinds series CEAG eLLK LED light fixture is an ideal source of general illumination, indoors or out, in Zone…
-
Capri ADCS & ADCC – Cable glands for flexible & rigid conduits
The ADCC and ADCS is a widely approved cable gland for use connecting a cable and conduit system. With a…
-
Champ CPMV LED Hazardous Area Wallpack Light Fixtures
The Crouse-Hinds series Champ CPMV is uniquely engineered to provide a low profile wallpack solution for hazardous lighting applications. It’s…